ATI’s F12/D Toxic Gas Transmitter is designed to measure more than 60 toxic gases, featuring the exclusive AutoTest* function that provides daily, reliable response checks to ensure system integrity. The F12D is highly customizable to suit almost every fixed mount toxic gas application.

For pricing please call AFC International at 800-952-3293, 219-987-6825 or fax 219-987-6826 or email sales@afcintl.com.

Description

Description

ATI’s F12/D Toxic Gas Transmitter provides a high level of confidence that your system is functional at all times. The Auto-Test feature provides an actual gas “bump test” every 24 hours, verifying system integrity. Not an electronic test of some kind but a true test of sensor response to gas.

For many toxic gases, ATI offers a unique sensor response testing system unmatched by any competitive gas detector. Even outdoors in high wind conditions, the Auto-Test system provides reliable response checks to ensure system integrity. Sensor response is verified with an actual gas sample that is generated on demand. Generators store run time information accessible to operators, and are automatically tested for compatibility with the installed electrochemical sensors.

F12 gas detectors provide useful features that simplify installation, operation, and maintenance. The 4-button keypad is used to configure the menu-driven setup pages. The display also provides alarm indication and complete menus for setting up operating parameters.

The F12iS is also available for hazardous locations.

*Dependent upon gas being monitored

The F12/D uses ATI smart sensors that allow easy interchangeability. Each sensor contains signal conditioning electronics and data memory. Sensors can be calibrated using a spare unit avoid using calibration gases in the plant. Sensors may also be returned to ATi for factory calibration, which is useful for gases that are costly or difficult to obtain. Each sensor adjustment (zero or span) is stored in sensor memory and can be reviewed on the F12D display. This data is very useful in assessing the sensor’s condition and estimating remaining sensor life.

For pricing please call AFC International at 800-952-3293, 219-987-6825 or fax 219-987-6826 or email sales@afcintl.com.

Features

  • Interchangeable sensors accommodating 60 different gas modules
  • Sensor verification with Auto-Test function
  • Test history is stored in sensor memory
  • LCD Graphic Display
  • Heated sensor option allows operation in high humidity
  • Remote sensor junction box with digital output allows sensor location up to 500 ft. from the F12D
  • Internal data logger stores gas values at user defined intervals from 1 to 60 minutes
  • Calibration history and calibration adjustments of zero and span are stored in sensor memory
  • F12iS variant is available with optional Hart® output
  • CE and RoHS Compliant

Specifications

Range User adjustable within limits of selected sensor module
Response Time Sensor dependent
Accuracy Generally ±5-10% of value, but limited by available calibration gas accuracy
Electronic Repeatability ±1% of full scale
Electronic Linearity ±0.5% of full scale
Zero Drift Less than 2% of full scale per month, non-cumulative
Span Drift Application dependent, but generally less than 3% per month
Alarm Relay Option Three SPST 5A@ 230 VAC resistive
Analog Output 4-20 mA, 600 ohms maximum at 24 VDC
Serial Interface HART digital signaling over the 4-20 mA current loop, Optional
Power DC/RS-485: 24-30 VDC, 100 mA max
115 VAC ±15%, 50-60 Hz, 6 VA max
230 VAC ±15%, 50-60 Hz, 6 VA max
12-30 VDC with relays: 240 mA max
Enclosure IP65 Polycarbonate with SS hardware. Weatherproof and corrosion resistant
Sensor Type Electrochemical for toxic gases and oxygen
Controls Four dome type push buttons, remote alarm reset input
Temperature -30° to + 60°C for toxics, -10°C minimum for oxygen sensor
Weight 1.5 pounds

Sensor Specifications

Gas
Range
Catalog No.
Acetic Acid
0-100/500 ppm
00-1045
Acid Gases
0-10/200 ppm
00-1038*
Acetylene
0-200/2,000 ppm
00-1057
Alcohol
0-50/500 ppm
00-1043
0-500/2,000 ppm
00-1044
Ammonia
0-50/500 ppm
00-1010*
0-500/2,000 ppm
00-1011
Arsine
0-500/2,000 ppb
00-1024
0-10/200 ppm
00-1025
Bromine 0-1/5 ppm 00-1000*
0-5/200 ppm
00-1001*
Carbon Monoxide
0-50/1,000 ppm
00-1012*
Chlorine
0-1/5 ppm
00-1002*
0-5/200 ppm
00-1003*
Chlorine Dioxide
0-1/5 ppm
00-1004*
0-1/5 ppm, low Cl2 Response
00-1425*
0-5/200 ppm
00-1005*
0-200/1,000 ppm
00-1359
Diborane
0-500/2,000 ppb
00-1026
0-10/200 ppm
00-1027
Dimethyl Amine
0-100/200 ppm
00-1450*
Ethylene Oxide
0-20/200 ppm
00-1039*
Fluorine*
0-1/5 ppm
00-1006*
0-5/200 ppm
00-1007*
Formaldehyde*
0-20/200 ppm
00-1040*
0-500/2,000 ppm
00-1349*
Germane
0-500/2,000 ppb
00-1028
0-10/200 ppm
00-1029
Hydrogen
0-1/10%
00-1013
0-500/2,000 ppm
00-1041
Hydrogen Bromide* 0-10/200 ppm 00-1455*
HC Sensor Specify Gas 00-1516
Hydrogen Chloride*
0-10/200 ppm
00-1017*
Hydrogen Cyanide*
0-10/200 ppm
00-1018*
Hydrogen Fluoride*
0-10/200 ppm
00-1019*
Hydrogen Peroxide*
0-10/100 ppm
00-1042*
0-200/2,000 ppm
00-1169
Hydrogen Selenide
0-500/2,000 ppb
00-1030
0-10/200 ppm
00-1031
Hydrogen Sulfide*
0-10/200 ppm
00-1020*
0-200/1,000 ppm
00-1469
Iodine*
0-1/5 ppm
00-1036*
0-5/200 ppm
00-1037*
Nitrogen Dioxide
0-10/200 ppm
00-1022*
Nitric Oxide
0-50/500 ppm
00-1021
Oxygen
0-5/25%
00-1014
Ozone*
0-1/5 ppm
00-1008*
0-5/200 ppm
00-1009*
0-200/1,000 ppm
00-1358
Peracetic Acid
0-1/5 ppm
00-1704
0-10/100 ppm
00-1705
Phosgene
0-1/5 ppm
00-1015
0-5/100 ppm
00-1016
Phosphine
0-500/2,000 ppb
00-1032
0-10/200 ppm
00-1033
0-200/2,000 ppm
00-1034
Silane
0-10/200 ppm
00-1035
Sulfur Dioxide
0-10/500 ppm
00-1023*

(*) Indicates Auto-Test available