SEC 3000 Gas Detector from Sensor Electronics

Description

Description

The SEC 3000 gas detector is a unique design combining intrinsically safe and explosion proof approved standards. This allows for quick and simple field installation of a calibrated sensor module into the gas detector in hazardous locations with power applied. The SEC 3000 sensor module retains operating parameters and calibration settings. Once the sensor module is plugged into the gas detector, the sensor module automatically uploads current information to the control board in the SEC 3000. Changing to a different type of gas sensor is accomplished by only changing the sensor module board. The existing housing and wiring remains intact.

An industry standard 4-20 mA analog output provides remote alarm, fault and calibration signals. The entire unit utilizes self-diagnostics, identifies problems and simultaneously transmits status.

The SEC 3000 can be used in conjunction with the SEC 3100 or SEC 3120 explosion proof transmitter. The SEC 3100 and SEC 3120 has a backlit LCD display, non intrusive local calibration, 4-20 mA output, optional relays, RS485 interface and intrinsic barrier.

Features

  • Compact low cost design
  • No field gas calibration required
  • Intrinsically safe and explosion proof
  • Universal control board
  • Interchangeable sensor modules for oxygen and toxic gases
  • Temperature compensated sensor
  • Stand alone gas detector with 4-20 mA output
  • Corrosion resistant 316 stainless steel housing construction
  • Long life electrochemical sensors
  • Can be mated with SEC 3100 transmitter or SEC 3120
  • Optional heater with closed loop temperature control ensures accuracy in low temperature applications
  • New 3000 AI
    -Drift Tracking intelligently identifies and removes drift from output signal
    -O.N.R. (Output Noise Rejection) identifies noise at the output and removes it

Applications

  • Petrochemical
  • Medical
  • Semi conductor
  • Mining
  • Pulp & paper
  • Offshore
  • Fertilizer
  • LNG & LPG processing
  • Waste water
  • Water treatment
  • Chemical
  • Automotive
  • Pharmaceutical
  • Refrigeration

Specifications

Gas
Range
Ammonia
0-200 ppm
Arsine
0-1,000 ppb
Bromine
0-2 ppm
Carbon Monoxide
0-100 ppm
Chlorine
0-10 ppm
Chlorine Dioxide
0-2 ppm
Diborane
0-1,000 ppb
Ethylene Oxide
0-20 ppm
Fluorine
0-2 ppm
Formaldehyde
0-20 ppm
Germane
0-1,000 ppb
Hydrogen
0-1,000 ppm
Hydrogen Chloride
0-20 ppm
Hydrogen Cyanide
0-20 ppm
Hydrogen Fluoride
0-10 ppm
Hydrogen Peroxide
Call
Hydrogen Selenide
0-1,000 ppb
Hydrogen Sulfide
0-100 ppm
Nitric Oxide
0-100 ppm
Nitrogen Dioxide
0-15 ppm
Oxygen
0-40% Vol
Ozone
0-2 ppm
Phosgene
0-2 ppm
Phosphine
0-1,000 ppb
Silane
0-20 ppm
Sulfur Dioxide
0-20 ppm

Unit Status Chart

Current
Output
Status
4-20
mA
Normal measuring mode
0.0
mA
Unit fault
0.8
mA
Unit warm up
1.2
mA
Zero drift fault
1.6
mA
Calibration fault
2.0
mA
Unit spanning
2.2
mA
Unit zeroing
4.0
mA
Zero gas level
5.6
mA
10% of full scale
8.0
mA
25% of full scale
12
mA
50% of full scale
16
mA
75% of full scale
20
mA
100% of full scale
>20
mA
Over range (>100%)

Specifications

Detection Method Toxic Gases – Electrochemical, galvanic or catalytic bead
Sampling Method Diffusion, optional sample draw
Output (digital) Interactive interface available on the calibration (white) wire
Output (analog) 4-20 mA (source type), max 1000 ohm load at 24 VDC supply voltage
Lower Detachable Limit 1% of full scale
Housing Construction 316 Stainless Steel, explosion proof
Accuracy ± 5%
Operating Voltage 24 VDC, operating range: 18 to 32 VDC measured at the detector head
Power Consumption 1.6 Watt Max
Max Current Draw 50 mA at 24 VDC
Operating Temperature -40° to 50°C at 0 to 99% RH, non condensing